← Back to the hardware range
RCT Power backup switching

RCTerra Grid Switching Cabinets

Seamless on and off grid switching for the RCTerra range. The GSC261 pairs with the Class 2.0 261 and the GSC1000 with the Pro 2.0 783 and 1044, so critical loads ride through a grid failure in under 20 milliseconds.

Under 20 ms
Switching time
250 kW
GSC261 power
742 kVA
GSC1000 capacity
IP54
Outdoor rated
RCT Power GSC261 grid switching cabinet, the backup switch for the RCTerra Class 2.0 261

What a grid switching cabinet does

Keeps the load up when the grid drops

When the grid fails, the cabinet switches the site load across to the RCTerra battery system, and back again when supply returns. Passive switching completes in under 20 ms and active switching is seamless, so production lines, cold rooms and IT loads do not notice.

Grid forming, generator ready

The GSC261 synchronises automatically, with VSG grid forming compatibility and adaptation to any generator set. Optional PV and diesel generator access ports let the site run as a managed microgrid, with an integrated bypass and a built in UPS for the auxiliary supply.

One cabinet per storage block

A single GSC261 serves one or two Class 2.0 261 cabinets at 250 kW. The GSC1000 is sized for the Pro 2.0 at 742 kVA, with a 721 A load port matched to the 500 kW 1044 build and the 375 kW 783 build. Both install on a foundation beside the storage block.

Managed through Ampaura Connect

Modbus communication into the PCS and Ampaura Connect, so the switch, the battery and the site load are monitored and controlled as one system. Both cabinets are IP54, forced air cooled and rated C4, with C5 available for coastal and industrial sites.

The two cabinets

RCT Power GSC261 grid switching cabinet for the RCTerra Class 2.0 261
GSC261-250-01, for the RCTerra Class 2.0 261
RCT Power GSC1000 grid switching cabinet for the RCTerra Pro 2.0 783 and 1044
GSC1000-742-01, for the RCTerra Pro 2.0 783 and 1044

Specification

Figures below are taken directly from the RCT Power GSC261 grid switching cabinet datasheet, revision April 2026, and the RCT Power GSC1000-742-01 grid switching cabinet manual, revision 1.0, July 2025. Each cabinet is an optional item ordered with its matching RCTerra storage block and connected to it by control and communication cables.

GSC261 · General
Model
GSC261-250-01
Compatible product models
1 or 2 units of RCTerra Class 2.0 261
Bypass function
Integrated
Switching time
Under 20 ms passive, 0 ms active
Overload capacity
110% for 1 minute
UPS power supply
1 kVA, 220 Vac
Isolation type
Non isolated
GSC261 · Grid side input
Rated voltage
400 Vac
Rated frequency
50 / 60 Hz
Rated power
250 kW
Rated current
360 A
THDu
Under 10%
GSC261 · Load side output
Rated voltage
400 Vac
Rated power
250 kW
Rated current
360 A
GSC261 · Battery side output
Rated voltage
400 Vac
Rated frequency
50 / 60 Hz
Rated power
250 kW
Rated current
360 A
THDu
Under 10%
GSC261 · Physical and operating
Operating temperature range
-25 to 55 C
Maximum operating altitude
Up to 4000 m
Dimensions, W x H x D
900 x 2000 x 1000 mm
Weight
500 kg
IP rating
IP54
Cooling
Forced air cooling
Communication
RS485
Design lifetime
20 years
GSC1000 · General
Model
GSC1000-742-01
Compatible product models
RCTerra Pro 2.0 783 and 1044
Nominal capacity
742 kVA
Rated working voltage
230 / 400 Vac
Working voltage range
Plus or minus 15%
Rated working frequency
50 / 60 Hz
Connection
Three phase + neutral + PE
Communication
Modbus, RS485 and CAN
GSC1000 · Switching and overload
Opening time
Under 20 ms
Closing time
Under 20 ms
Maximum output current of port
Load 721 A, battery 350 A
Short time overload tolerance
1.5 Ie for 20 min, 2 Ie for 10 min, 5 Ie for 10 s
Rated impulse withstand voltage
6 kV
Power frequency withstand voltage
2500 V for 5 s
GSC1000 · Physical and operating
Operating temperature range
-20 to 45 C
Relative operating humidity
0-100% RH, non condensing
Maximum operating altitude
Up to 2000 m
Dimensions, W x H x D
1304 x 2065 x 1204 mm
Weight
700 kg
IP rating
IP54
Corrosion proof grade
C4, C5 optional
Noise level
56 dB
Cooling
Forced air cooling

Datasheets

The RCT Power documents as issued. The GSC1000 manual includes the foundation drawing, cable sizes and the control wiring to the Pro 2.0 PCS. If you need the GSC261 installation guide or a single line diagram for your site, ask and we will send it.

Specify it with the battery

A grid switching cabinet is an optional item on every RCTerra quote. Tell us which loads need to ride through an outage and we will size the battery and the switch together, then model the whole site in Ampaura Designer.