← Back to the hardware range
RCTerra Max 1.0

RCTerra Max 1.0 4000

A twenty foot containerised DC energy storage block, 4,073 kWh, with the battery modules and liquid cooling installed at the factory and a hybrid cooling design that keeps the parasitic load down.

4,073 kWh
Nominal energy
20 ft high cube
Format
38 t
Approximate weight
8,000 cycles
Cell cycle life
RCTerra Max 1.0 4000 containerised battery energy storage system

Built for the top end

Factory built, container delivered

Battery modules and the liquid cooling system are pre installed in a standard twenty foot ISO container. What arrives on site is a finished block, not a kit.

Hybrid cooling

A liquid cooling chiller works with HVAC, and supplementary air cooling reduces the power the system spends cooling itself. Less parasitic load means more of the stored energy reaches the site.

Explosion protection to NFPA 69

Explosion proof ventilation compliant with NFPA 69, with detection for both smoke and flammable or explosive gas.

A DC block, not an all in one

The Max is a DC energy storage system. It pairs with an external power conversion system chosen for the site, which is what makes it flexible at utility scale and why the AC rating is set by the inverter you put with it.

The Max 1.0 container

RCTerra Max 1.0 container three quarter view
Three quarter view
RCTerra Max 1.0 container side elevation
Side elevation
RCTerra Max 1.0 container showing the cooling end
Cooling end
Walkthrough footage from RCT Power. Silent.

Specification

Figures below are taken directly from the RCT Power RCTerra Max 1.0 4000 datasheet, IEC and UL, revision April 2026. This is a DC system, so AC ratings depend on the power conversion system specified with it.

General
Nominal energy
4,073 kWh
Maximum charge and discharge rate
0.1 to 0.5 C
Operating temperature range
-30 to 50 C
Dimensions, W x H x D
6058 x 2896 x 2438 mm
Footprint
20 ft high cube ISO container
Weight
Approximately 38 t
IP rating
IP55, outdoor use
Corrosion proof grade
C4, C5 optional
Noise level
84 dBA at 1 m at 50 Hz, 86 dBA at 60 Hz
Auxiliary load voltage
480 V 60 Hz, or 380-415 V 50-60 Hz, 3P4W
BMS and EMS
Integrated
Cycle lifetime of cell
At least 8,000 cycles to 70% SOH at 25 C
Battery, DC side
Battery rack quantity
10
Packs per rack
8
Pack structure
1P52S
Battery cell capacity
306 Ah
Energy per pack
50.918 kWh
Battery type
LiFePO4
DC side rated voltage
1331.2 Vdc
Output DC voltage range
1164-1500 Vdc
Cooling method
Liquid cooling
Cooling and safety
Cooling design
Liquid cooling chiller plus HVAC, with supplementary air cooling
Explosion protection
Explosion proof ventilation design compliant with NFPA 69
Detection
Smoke detection and flammable or explosive gas detection
Standards
Standards
EN 62477-1, IEC 62040-1, EN 61000-6-2 and -4, EN 55011, CISPR 11, IEC 62933-5-2, IEC 62933-5-1 and -2-1, IEC 61439-1 and -2, UL 9540, UL 9540A, NFPA 69, UN 38.3
NSW PDRS
Certified for NSW PDRS BESS5

Spec sheets

The RCT Power datasheet covers both the IEC and UL builds. Foundation drawings, transport details and PCS pairing notes are available on request.

Utility scale starts with a conversation